OT / ICS Protocol Explorer

A reference for the protocols that actually run the physical world — fieldbuses, SCADA links and substation buses. For each one: default ports and transport, where it sits in the Purdue model, whether it authenticates or encrypts anything natively, its documented weaknesses, what an attacker who reaches it can do, and how to detect abuse. Search, filter, expand any protocol for detail, and export the filtered set to CSV. Everything runs in your browser — nothing is sent anywhere.

20
Protocols
17
No native auth
18
No native encryption
23
Unique IP ports

Purdue-level distribution (filtered)

20 shown
Level 0–1 · Field / process11Level 1–2 · Control (PLC/RTU)6Level 2–3 · Supervisory / SCADA3Level 3–4 · Operations / IT-OT0
BACnet
Dominant building-automation protocol (HVAC, lighting, access); BACnet/IP is unauthenticated and broadcast-heavy.
47808/udp, Serial0-1
No authNo enc
CC-Link / CC-Link IE
Mitsubishi-led open fieldbus (serial) and Gigabit industrial Ethernet (IE); dominant in Asian manufacturing.
Serial, Ethernet (L2)0-1
No authNo enc
CIP Safety / FSoE (Safety fieldbus)
Functional-safety "black channel" protocols (SIL-rated) layered on top of EtherNet/IP, EtherCAT or PROFINET.
2222/udp, Ethernet (L2)0-1
No authNo enc
CODESYS (Gateway / V3 protocol)
The IEC 61131-3 runtime embedded in hundreds of OEM PLCs; its programming/gateway protocol has a long CVE history.
1217/tcp, 11740/tcp, 1200/tcp1-2
No authNo enc
DNP3
Electric/water SCADA protocol with event reporting and time-stamping; optional Secure Authentication rarely enabled.
20000/tcp, 20000/udp, Serial1-2
No authNo enc
EtherCAT
High-speed "processing on the fly" industrial Ethernet; a single L2 segment with no node-level security.
Ethernet (L2), 34980/udp0-1
No authNo enc
EtherNet/IP (CIP)
ODVA protocol carrying CIP over Ethernet; dominant in Rockwell/Allen-Bradley plants, no native security.
44818/tcp, 2222/udp, 44818/udp0-1
No authNo enc
HART / WirelessHART
Digital signalling layered over 4–20 mA field wiring; WirelessHART (IEC 62591) is the secured mesh variant.
5094/tcp, 5094/udp, Serial, Radio0-1
No authNo enc
IEC 60870-5-104
European electric-utility tele-control protocol; 104 is the TCP profile of the 101 serial standard, unauthenticated.
2404/tcp, Serial1-2
No authNo enc
IEC 61850 (MMS / GOOSE / SV)
Substation automation suite: MMS client/server (TCP), plus layer-2 GOOSE and Sampled Values for protection.
102/tcp, Ethernet (L2), Ethernet (L2)0-1
No authNo enc
M-Bus / Wireless M-Bus
European utility metering bus (heat/gas/water/electric); wired is unauthenticated, wireless M-Bus adds optional AES.
Serial, Radio0-1
No authNo enc
MELSEC / SLMP (MC Protocol)
Mitsubishi MELSEC PLC communication (MC Protocol / SLMP) for device read/write and remote control.
5007/tcp, 5006/udp1-2
No authNo enc
Modbus (RTU / ASCII / TCP)
The oldest and most widespread fieldbus/SCADA protocol; register read/write with no security whatsoever.
502/tcp, 502/udp, Serial0-1
No authNo enc
Niagara Fox (Tridium)
Proprietary protocol of the Tridium Niagara building-automation framework; widely internet-exposed historically.
1911/tcp, 4911/tcp2-3
AuthEnc
OMRON FINS
OMRON PLC protocol for memory access and CPU control; unauthenticated over UDP/TCP.
9600/udp, 9600/tcp1-2
No authNo enc
OPC Classic (DA / HDA / A&E)
Legacy Windows DCOM-based OPC; notorious for dynamic RPC ports and a huge attack surface.
135/tcp, TCP2-3
AuthNo enc
OPC UA
Modern, platform-independent OPC with a real security model — but frequently deployed in insecure "None" mode.
4840/tcp, 4843/tcp2-3
AuthEnc
PROFIBUS (DP / PA)
Classic RS-485/MBP serial fieldbus; physically isolated but completely unauthenticated on the wire.
Serial, Serial0-1
No authNo enc
PROFINET
Siemens-led real-time industrial Ethernet; layer-2 real-time channel is unauthenticated and spoofable.
34962/udp, 34963/udp, 34964/udp, Ethernet (L2)0-1
No authNo enc
S7comm / S7comm-Plus
Siemens SIMATIC S7 PLC protocol over COTP/TPKT; S7comm is unauthenticated, S7comm-Plus adds (breakable) anti-replay.
102/tcp1-2
No authNo enc

Reference material for defenders and architects. Security posture reflects base-protocol behaviour; secure variants (OPC UA security policies, DNP3 SAv5, CIP Security, IEC 62351, BACnet/SC) change the picture when actually deployed and configured. Always verify against your own equipment and the current vendor and CISA advisories.

Loading…

Sample report · illustrative data

Sample result: OT protocol profile

Example: searching for "modbus" and opening the Modbus (RTU / ASCII / TCP) entry.

Protocol profile

Ports
502/tcp (Modbus/TCP), 502/udp (rare), serial for RTU and ASCII
Purdue level
Levels 0-2 (field devices, PLCs, SCADA polling)
Native authentication
No
Native encryption
No

Weaknesses listed

  • Any node that can reach port 502 can read or write any coil or register; function codes are the whole access-control model.
  • No session, nonce or sequence number, so commands are trivially replayable.
  • The unit ID is routing, not identity, so it cannot be trusted as an authenticator.

What an attacker can do

  • Read process values to map the process.
  • Write coils or registers to force outputs or change setpoints.
  • Replay previously captured write commands.

Made-up example data. Your own run uses your inputs. Downloads of the full report need Pro.