Danfoss AK-SM800A Zero-Days: 6 Unpatched Flaws, What to Do

November 18, 2026 · Team PlayCISO
TL;DR · the short version

Dutch security firm Midnight Blue says researcher Carlo Meijer found six pre-authentication remote code execution zero-days, all stack-based buffer overflows, in the Danfoss AK-SM800A, the system manager that runs refrigeration and HVAC in many supermarkets. It says every firmware version up to and including 5.3.2 is affected. CVE IDs are pending, technical details are withheld while it coordinates with Danfoss, and no fix is available. Midnight Blue does not say these flaws were used in the attacks on internet-exposed fridge controllers in Europe since 11 October. Danfoss's own update guide says the unit should not be reachable from the public internet on any software version, Strict Mode included. Take controllers off the internet, put remote access behind a VPN, segment them from store IT and change default passwords.

Put it into practice
Find which controllers are exposed before anyone else does
Paste your own scan or asset export and see which OT devices are reachable from where.
Open the OT exposure parser

Dutch security firm Midnight Blue says it found six pre-authentication remote code execution zero-days in the Danfoss AK-SM800A, the system manager that runs refrigeration and HVAC in many supermarkets. It says every firmware version up to and including 5.3.2 is affected. There are no CVE IDs and no patch yet, and Midnight Blue does not claim the flaws have been exploited. Its advice, and Danfoss's own: take these controllers off the internet now.

Who this is for: retail, food, pharmacy and facilities leaders, the OT and IT teams that run store controllers, and the refrigeration contractors who maintain them remotely.

Based on Midnight Blue's write-up, Danfoss's AK-SM800A update guide and CISA's 2025 advisory for earlier flaws, with national-agency positions as reported by The Hacker News. PlayCISO is not affiliated with Midnight Blue or Danfoss. Facts as reported on 18 November 2026.

Confirmed vs not yet known

Midnight Blue says: six pre-authentication remote code execution flaws (stack-based buffer overflows); all firmware up to and including 5.3.2; CVEs pending; no patch; details withheld during coordinated disclosure with Danfoss.

Danfoss says (update guide): the AK-SM800A "should not be directly reachable from the public internet", on every software version, including with Strict Mode on.

Not established: whether 5.4.0 fixes anything (the researchers, per The Hacker News, believe it does not; Danfoss's 5.4.0 material mentions no fix), when a patch will ship, and any exploitation of these six flaws.

Separate story: attacks on internet-exposed Danfoss and Copeland fridge controllers in Europe since 11 October 2026. No source we read ties them to these zero-days.

What Midnight Blue found

  • Six flaws, no login needed. Midnight Blue lists the type as "multiple (6) stack-based buffer overflows" reachable before authentication, found by researcher Carlo Meijer. The Hacker News reports he found them in under an hour of manual review of firmware Danfoss offers for download.
  • Strict Mode is not enough. Strict Mode (HTTPS plus session tokens) fences off most of the unauthenticated surface, Midnight Blue says, but at least one flaw is in the session control mechanism itself.
  • Missing basic hardening. Midnight Blue says the main binary lacks stack canaries and position-independent code, and that the controller does not use the processor's secure boot, which it says would allow persistent implants and bricking.
  • No details yet. Midnight Blue is withholding technical details until disclosure with Danfoss is complete. We give none here either.

How this differs from the earlier Danfoss CVEs

These are new. Earlier AK-SM800A flaws do have CVEs and fixes: CISA's ICSA-25-140-03 covers CVE-2025-41450 (improper authentication, fixed in R4.2) and CVE-2025-41451 and CVE-2025-41452 (fixed in 4.3.1), reported by Claroty Team82. Midnight Blue says public proofs of concept for CVE-2025-41450 appeared within 48 hours of the French attacks. Older units that never got those updates are exposed twice over.

Useful next, if this was relevant to you

Showing 1 of 3: CISO Readiness Scorecard

Timeline

DateWhatSource
20 May 2025 (updated 26 Aug 2025)CISA advisory for earlier AK-SM 8xxA flaws CVE-2025-41450, -41451, -41452CISA
11 Oct 2026Attacks on internet-exposed Danfoss and Copeland refrigeration controllers begin in FranceMidnight Blue
2 Nov 2026Second wave of attacks across EuropeMidnight Blue
Nov 2026Midnight Blue publishes the six AK-SM800A zero-days; CVEs pending, no patchMidnight Blue
Nov 2026Danfoss lists software package 5.4.0 with stricter password rules; its update guide repeats that the unit must not be internet-reachableDanfoss
16 Nov 2026The Hacker News reports German, Belgian and Irish authorities' warnings and that Danfoss's advisory page lists none for the six flawsThe Hacker News

What security leaders should do this week

  1. Find every controller. Build the list from your own records: store asset registers, contractor contracts, and network and firewall data. Include units reached through a refrigeration integrator's 4G modem or cellular router, which Midnight Blue singles out. Rank them with the OT asset ranker.
  2. Take them off the internet. Danfoss's guide: remote access "through a VPN only", with tunnels started from the site rather than inbound connections. Midnight Blue calls tight IP allowlists an interim measure and says broad geofencing or blocklists are "not sufficient". Check what is reachable from where with the OT exposure parser.
  3. Segment. Put refrigeration and building controllers on their own network zone, apart from point of sale and store IT. Decide in advance which controllers you can isolate without spoiling stock, using the safe-to-isolate matrix.
  4. Change defaults and keep Strict Mode on. Replace default and shared passwords (5.4.0 enforces complex ones) and confirm Strict Mode is enabled. Neither is enough alone, but both close the older, already-public holes.
  5. Patch what can be patched, then watch for the fix. Bring units to a supported release for the 2025 CVEs, and track Danfoss's security advisories page for the six new ones. Ask your contractor who will apply it and when.
  6. Plan for a bad night. Agree how stores spot unexpected defrost cycles and what the manual fallback is. Our Modbus write PCAP lab shows what an unauthorised control change looks like on the wire, and the BMS / refrigeration config auditor checks a controller's settings.

Background on why fridges are OT: the French fridge attacks. This week's other incidents: 17-18 November roundup.

FAQ

What did Midnight Blue find in the Danfoss AK-SM800A?

Six pre-authentication remote code execution vulnerabilities, which it classes as stack-based buffer overflows. Midnight Blue says at least one is in the session control mechanism, so Strict Mode does not fully protect against it. It is withholding technical details while it coordinates disclosure with Danfoss.

Which AK-SM800A firmware versions are affected?

Midnight Blue says all versions up to and including 5.3.2. It tested 5.3.2 and ran its proof of concept on 3.3.0. The Hacker News reports the researchers believe 5.4.0, Danfoss's newest release, is also affected; Danfoss's 5.4.0 material we read mentions no vulnerability fix.

Is there a patch or CVE for the Danfoss AK-SM800A zero-days?

Not yet. Midnight Blue lists the CVEs as pending and reports no patch. The Hacker News reports Danfoss's advisory page lists no advisory for the six flaws as of 16 November 2026.

Were these flaws used in the European supermarket fridge attacks?

No source says so. Midnight Blue describes waves of attacks on internet-exposed Danfoss and Copeland controllers since 11 October 2026 but does not link its six zero-days to them, and The Hacker News reports the national agencies have no information about exploitation of the new flaws.

Does Strict Mode protect the AK-SM800A?

Partly. Midnight Blue says Strict Mode fences off most of the unauthenticated attack surface but not the session control flaw. Danfoss's update guide says the unit should not be directly reachable from the public internet on any software version, including those with Strict Mode enabled.

What should operators of Danfoss AK-SM800A controllers do now?

Remove internet exposure first: remote access only through a VPN initiated from the site, or tightly restricted allowlists as an interim step. Inventory every controller, including those reached through an integrator's 4G modem, segment them from store IT and point of sale, change default passwords and keep Strict Mode on.

Where sources differ

  • Midnight Blue says Strict Mode has been the default since firmware 4.0; Danfoss's update guide says it is enabled by default from software package 4.3.1.
  • Whether 5.4.0 is affected: the researchers say likely yes (per The Hacker News); Germany's BSI first said it was not affected and then said it could not rule it out (also per The Hacker News). Danfoss has not said.

Sources

As of 18 November 2026. We will add the CVE IDs and fixed versions when Danfoss publishes them.

Find which controllers are exposed before anyone else does
Paste your own scan or asset export and see which OT devices are reachable from where.
Open the OT exposure parser
Take this with you
What Midnight Blue found · How this differs from the earlier Danfos… · Timeline · What security leaders should do this week · Where sources differ · Sources

Ready to practise the decisions these articles describe?

Run your first Cyber War Room free →

Pro