A pasteuriser setpoint changes and nobody on shift did it
The prompt — read this to the room
At 02:15 the HMI at a regional dairy shows the pasteuriser hold-tube temperature setpoint has moved from 72.5°C to 68.0°C. Nobody on the night shift admits to changing it. The change log names the engineering workstation's shared login, and that workstation sits in a locked, empty office. The flow-diversion valve worked and no under-temperature milk left the line, but 9,000 litres are now held in a silo pending a decision. The morning tanker leaves at 06:00. Was this an attacker, a scheduled job or a mistake, and how do you find out without destroying the evidence?
Who to involve
Most important first.
- OT / plant engineer
- Incident response lead
- SOC analyst
- IT operations
- Physical security / facilities
- CISO / Head of security
What it tests
- Restore a known-safe process state without losing the evidence needed to explain the change.
- Separate the three explanations (intrusion, automation, human error) using logs that actually exist.
- Show which OT logs, project backups and access records the team can produce within an hour.
- Decide on product release with food-safety and security evidence side by side.
Outline of activities
- 1The alarm: an unexplained setpoint change and product on hold
- 2Make it safe, then preserve: what to capture before anyone touches the PLC
- 3Three hypotheses tested against logs, badges and network data
- 4The product decision and who signs it
- 5Hardening the engineering workstation and change control
Free preview from the run sheet
First inject · minute 15
PLC change log extract
PLC-PAST-01 change log: 01:58:41 Write HoldTube_SP 72.5 -> 68.0 Source: EWS-01 User: eng_shared. 01:58:44 Download complete. No other writes since 19:12 yesterday.
Questions for the OT / plant engineer
- What does the process look like right now, and what else could the person who changed the setpoint have changed?
- How do you compare the running PLC logic against a known-good copy, and where is that copy?
- Are setpoint limits enforced in the PLC, or only on the HMI?
- What would you need to see to sign that nothing else on the line was changed?
Built on: NIST SP 800-82r3 Guide to Operational Technology (OT) Security; ISA/IEC 62443-2-1 and 62443-3-3 (security program and system requirements); CISA Primary Mitigations to Reduce Cyber Threats to Operational Technology (2025); NIST SP 800-61r3; Codex Alimentarius General Principles of Food Hygiene (HACCP annex).
The full run sheet below has every timed inject, the facilitator guide and questions for each role.
Run sheet
The facilitator's timeline of execution, the detailed steps for running the session and the questions to ask each person.